The
Indian Electricity Rule 116 is modified for mines. It says “The earth
fall current should not be more than 50 Amp. In 3.3 KV or 6.6 KV system
in mines”. The suitable Neutral Grounding Resistance (NGR) should be installed betwseen neutral point (star point) and the ground to restrict the earth fault current to 50 Amps. In 3.3 KV system resistance of 38 ohms, 100 KW, 5 sec & in 6.6 KV system resistance of 76 ohms, 200 KW, 5 sec will be installed. By installing these resistance fault current can be restricted to maximum 50 Amps.
In outdoor
distribution station there are many possibilities of damage to the
neutral grounding connections due to various environmental effects
causing open circuit or burning of NGR. This is a very dangerous
continuity i.e. totally floating type. This may also result in failure
of earth-leakage protection operating through neutral CT as the leakage
current may not be able to flow through open circuit of neutral
grounding connection.
To prevent this type of failure, Fail Safe Relays must be installed. The fail safe relay will continuously monitor the continuity of NGR and neutral grounding connections and will trip the feeder circuit breaker as and when any open circuit occurs in neutral grounding connection or in NGR. The fail safe relay will ensure fail safe operation of neutral grounding system. |
||
FAIL SAFE RELAY (NGR-MONITORING AND PROTECTION RELAY) | ||
A device called as Fail Safe Relay
(NGR-Monitoring and Protection Relay) has been developed and made
specifically for the fail safe condition. It has a highly insulated
sensor. This sensor is connected to the neutral terminal of the
transformer. The sensor has also the capacity to protect the relay from
any sudden transient peak voltage.
This relay ensures the fail-safe function of restricted neutral grounding system. It continuously monitors through its sensor, the continuity of N.G.R. (or variation in resistance value of NGR) as well as the continuity of neutral grounding connections. It trips the circuit breakers as and when any open circuit (or variation in resistance value) occurs in the N.G.R., in the neutral grounding connections or in the relay ground and sensor connections occur. This relay provides earth fault protection also to save the N.G.R. The relay senses earth fult current by its sensor. When the fault current exceeds the limit, the relay operates to trip the circuit breaker. The relay by it’s own earth-fault feature protects the N.G.R. independently. |
||
NGR MONITORING CUM PROTECTION REALY AND EARTH LEAKAGE RELAY THE TRIPPING CONDITIONS: | ||
|
||
Smart Fail-Safe Relay with Neutral Grounding Resistor Monitoring Relay,& Ground Fault Monitoring Relay | ||
In the Neutral Grounding Resisitor
systeam, continuous monitoring of Neutral Grounding Resistor is Must (as
per DGMS) to achive Fail-safe working
condition, Smart Fail-safe Relay (Continuosly Monitoring Relay of
Neutral Grounding Resistor) works on the
principle of the continuous monitoring Neutral Grounding Resistance
and continuously monitors the connection
between Neutral to Ground by injecting the low frequency signals
through the sensor. The system has
Specific indication for the different faults conditions. It also
continuously
monitor and indicate current passing
through the Neutral to Grounding Resistor(NGR), with the facility to set
trip value of current from 1 Amp. to 9.9
Amp. (as requaired by DGMS) and also the memory to hold the fault
current and votage at the time of tripping the relay. The smart
fail-safe relay is also check for the connections of the CT connected
periodicaly (every hour) for the fullproof fail-safe operation.
|
||
|
||
No external power supply or test equipment is required. Test and Reset can be by means of the buttons mounted on the cover. Source |
NEUTRAL GROUNDING RESISTOR AND FAIL SAFE RELAY
Subscribe to:
Post Comments (Atom)
can i get contact details of Mr Baldev Chaudhary
ReplyDelete